MATEŞ TRSA Counter Setting Desk:
MATEŞ ELEKTRONİK, with its 30 years of experience in the production of Counter Setting Table, has installed its own production TRSA Counter Adjustment Table in many institutions in Turkey and in various countries. Meter Adjustment Desk, identified with the MATEŞ ELEKTRONİK brand in Turkey, has become known as “MATES” over the years. TRSA has been redesigned in an all electronic structure using the latest measurement technologies to meet today's requirements. TRSA comes with a computer software that gives full control of the device and an energy etalon with a touch screen.
The devices are designed in line with the directives of the Ministry of Industry and Technology and are produced with the permission of the ministry.
TRSA USERS:
TRSA is already in use in many provinces of Turkey and various other countries.
Almost all of the meter manufacturers and energy distribution companies in Turkey use TRSA. The majority of TRSA Meter Setting Desks older than 15 years of age, which are all electronic, are still in active daily use.
SUITABILITY:
(0.2 – 0.5 – 1 – 2 class) Electronics and Electromechanics
x5A meters
Direct (with internal shunt) counters (*)
| Technical Specifications of Three Phase Devices: | |
| Measurement Accuracy (*) | 0.03% reading + 0.02% full scale = 0.05% |
| Voltage Output stability Sensibility Frequency Distortion | 3x 20…300V >0.1% > 0.3% full scale 45…65Hz > 1% (linear load) |
| Current Output stability Sensibility Frequency Distortion | 3x 5mA…100A >0.1% > 0.5% full scale 45…65Hz > 1% (linear load) |
| Phase Angle | It can be adjusted between 0-360° with a sensitivity of 0.1°. |
| Device Supply Voltage | 220V (-12% …+ 8%) 50 Hz, max. 16A |
| Technical Specifications of Single Phase Devices: | |
| Measurement Accuracy (*) | 0.03% reading + 0.02% full scale = 0.05% |
| Voltage Output stability Sensibility Frequency Distortion | 1x 20…300V >0.1% > 0.3% full scale 45…65Hz > 1% (linear load) |
| Current Output stability Sensibility Frequency Distortion | 1x 5mA…100A >0.1% > 0.5% full scale 45…65Hz > 1% (linear load) |
| Phase Angle | It can be adjusted between 0-360° with a sensitivity of 0.1°. |
| Device Supply Voltage | 220V (-12% …+ 8%) 50 Hz, max. 16A |
(*) Single-Phase TRSA models are only suitable for single-phase meters. For the tests of three-phase direct (with internal shunt) meters, the device must be purchased with optional Current Isolation Transformers.