Homepage ›› Companies ›› Emge Electro Mechanical Devices Industry Inc. ›› EG-32 36kV Line Grounding

Emge Electro Mechanical Devices Industry Inc.

Adres: 1211. CADDE (ESKİ 815) 1

Tel 1: 0 (312) 385 20-23

Tel 2: 0 (312) 354 92-71

Faks:

Email 1: emge@emge.com.tr

Email 2: mustafa@emge.com.tr

Email 3: satis@emge.com.tr

Web: www.emge.com.tr

EG-32 36kV Line Grounding

Eg-32 36Kv Line Grounding

DEFINITION

EG-32 Line grounding equipment is a system that ensures the life safety of employees by short-circuiting the line and grounding it while operating in energy-carrying lines and centers. OPERATION EG-32 Line grounding equipment clips are attached to each phase of the line and the branch cables of the clips are combined with the landing cable and short-circuited 3 phases. By connecting the down cable to the grounding cable, all 3 phases of the line are grounded. This protection is made from both sides of the studied area.

USE

At the beginning and end of the working area, the grounding stake is first driven into a suitable ground at a distance sufficient for the cable length. The cable on the reel is opened and the free end of the cable is firmly clamped to the grounding stake with a vise. A clip head is attached to the grounding stand, the clips are attached to this head, and the clips are attached to the line by pushing them from below, by holding them in such a way that the mouths of the clips are below the line with the help of the stand. The clip attached to the line automatically leaves the stanka head and stays on the line. After all three clips are attached in this way, the line is short-circuited and grounded. Before connecting the equipment on the line, all screw connections on the equipment circuit should be checked and tightened if any are loose. After the line is grounded, it is worked on, when the work is finished, the studs in the stanka head are inserted into the hole of the clips and the clips are pulled down, the clips come out of the line. After the equipment leaves the line, the line is taken into service. While working on the line, a grounding equipment in the direction of energy is sufficient to prevent voltage being applied to the line by wrong maneuvers, but it is beneficial to provide life safety by making a second grounding at the end against the danger of atmospheric voltage according to climatic conditions. The landing cable of the equipment is 16 meters long and is sufficient to reach medium voltage lines. The clips can be attached to lines with a diameter of 3-20 mm. 16 mm2 cable withstands up to 4000 amps for 1 second. Stanka is used between 3-75 kV.

CASING

Cable and stank should not be left out in direct sunlight and should be protected against rust and moisture in their packaging in non-humid places.

PACKAGING mm
STANKA 150 x 230 x 100
TOOL BOX 230 x 500 x 210
Equipment Weight: 12kg.
Get Info