In sensitive applications such as operating rooms, pharmaceutical industry, chemical industry, food production, electronics industry and research laboratories, a ventilation system should be used in accordance with the conditions specified in the standards.
Laminar flow blowing systems meet the requirements in accordance with the conditions specified in the standards with the hygienic ventilation technique in the distribution and filtering of the air.
Its assembly is done on the ceiling of the operating room so that it is above the operating table.
The system consists of stainless steel air distribution box, hepa filters, transparent air distributor (laminator) and operating room pendant lamp.
Laminizer is made of special production textile. The laminator, which is fixed after being stretched on the aluminum frame, is fixed to its slot in the plenum cell by means of latches. Laminarizers can be easily disassembled and reassembled for hepa filter replacement or periodic maintenance and cleaning.
The laminator provides a laminar (vertical) air flow towards the operating table.
Existing particles and microorganisms in the airflow area are immediately removed from the environment, providing a high degree of cleanliness around the operating table.
The plenum box is produced from kiln-dried antistatic powder coated DKP sheet. It can also be produced unpainted from stainless steel or aluminum upon special request. Inside the plenum box, there are two to four hepa filter slots, depending on the size of the laminar ceiling unit.
Hepa filters are mounted to their slots in the plenum cell with special frames that provide impermeability. Sealed round damper at the inlet of HEPA filter boxes